EUROLYZER® S1 Allrounder Set (O2E, CO-high, draft)

P00179

Robust and high quality flue gas analyzer set to setup oil, gas and solid heating systems.  




Back


  • Large HiRes display offers best readability and clear menu navigation, optimally protected by scratch-resistant armored glass.
  • Latest ECOx sensor technology with long service life, optimized calibration phase and short response time
  • Robust CO cell with measuring range up to 40,000 ppm
  • Features Bluetooth® and QR code data transmission to the EuroSoft® connect App
  • Extendable with CAPBs® units and high-quality accessories for all types of service measuring tasks

 

The EUROLYZER® S1 Allrounder Set perform accurate measurements of O2, COhigh, temperatures, pressure (draft) as well as precise calculation of various parameters such as lambda, combustion efficiency (Eta), flue gas loss (qA), dew point and CO2

 

Scope of delivery
M05231013 EUROLYZER® S1 (O2E, COhigh, draft, Bluetooth®)
500268 Flue gas probe with draft, 170 mm
500190 Condensate filter cartridge
523493
Power supply unit
524697
Charging cable
521844
Air sensor
500208
Filter set
500900
L-Boxx case with document compartment



O2 (oxygen)
Measuring range
0 to 21.0 vol.-%
Accuracy
±0.2 vol.-% RDG
Resolution
0.1 vol.-%
Response delay (t90) < 30 seconds
CO (carbon monoxide) with H2-compensation
Measuring range
0 to 4,000 ppm (max. 10,000)
Accuracy
±5 ppm (< 50 ppm)
±5 % RDG (> 50 ppm)
Resolution
1 ppm
Response delay (t90) < 60 seconds
CO2 (carbon dioxide)
Measuring range
0 to CO2 max.
Accuracy
±0.2 vol.-%
Resolution
0.1 vol.-%
Response delay (t90) < 30 seconds
Flue gas temperature
Measuring range
0 to 1,150 °C
Accuracy
±1 °C + 1 digit (< 300 °C)
±1 % RDG (> 300 °C)
Resolution
0.1 °C
Combustion air temperature
Measuring range
-20 to 200 °C
Accuracy
±3 °C + 1 digit (-20 to 0 °C)
±1 °C + 1 digit (0 to 200 °C)
Resolution
0.1 °C
Option: Draft/differential pressure
Measuring range
±70 hPa (draft)
±150 hPa (diff. pressure)
Accuracy ±0.02 hPa (< 2.00 hPa)
±1 % RDG (> 2.00 hPa)
Resolution
0.01 hPa (< 20 hPa)
0.1 hPa (> 20 hPa)
Max. overload 1350 hPa
Response delay (t90) < 10 seconds
Option: Pitot
Measuring range 0.5 to 70 m/s
Accuracy ±0.8 m/s
Resolution 0.1 m/s
Response delay (t90) < 20 seconds
Option: NO (nitrogen oxide)
Measuring range
0 to 5,000 ppm
Accuracy
±5 ppm (< 50 ppm)
±5 % RDG (> 50 ppm)
Resolution
1 ppm
Response delay (t90) < 60 seconds
Option: NOlow (nitrogen oxide low)
Measuring range
0 to 300 ppm
Accuracy
±2 ppm (< 40 ppm)
±10 % RDG (> 40 ppm)
Resolution
0.1 ppm
  < 60 seconds
Option: COhigh (carbon monoxide high)
Measuring range
0 to 4.0 Vol.-% (= 40,000 ppm)
Accuracy
±10 ppm
±5 % RDG
Resolution 0.001 Vol.-% with CO/H2 sensor
1 ppm without CO/H2 sensor
Response delay (t90) < 60 seconds
Option: NO2 (nitrogen dioxide)
Measuring range 0 to 500 ppm
Accuracy
±10 ppm (< 100 ppm)
±10 % RDG (> 100 ppm)
Resolution 0.1 ppm
Response delay (t90) < 60 seconds
Option: SO2 (sulfur dioxide)
Measuring range 0 to 5,000 ppm
Accuracy
±10 ppm (< 200 ppm)
±5 % RDG (> 200 ppm)
Resolution 1 ppm
Response delay (t90) < 60 seconds
Option: SO2low (sulfur dioxide)
Measuring range 0 to 2,000 ppm
Accuracy
±5 ppm (< 50 ppm)
±10 % RDG (> 50 ppm)
Resolution 0.1 ppm
Response delay (t90) < 60 seconds

Set overview
 




Systronik

EuroSoft® connect for iOS and Android

The free EuroSoft® connect App allows to transmit measured values to iOS and Android smartphones or tablets via QR code or Bluetooth®.


to the product
Systronik

EuroSoft® connect for Windows

The EuroSoft® connect software allows you to transmit measured values to the PC via microSD card and control the instrument remote via Bluetooth®


to the product












Our recommendations


Systronik

BLUELYZER® ST Allrounder Set (CO+ up to 20,000 ppm, draft)

Flue gas analyzer set for all fuels to set up heating systems.


to the product
Systronik

EUROLYZER® S1 NOX Set (O2E, CO/H2+, NO, Draft, Pressure)

Professional and robust flue gas analyzer set to service and inspect oil, gas and pellets-fired heating systems as well for NOx measurements (e.g. for CHPs). 


to the product
Systronik

EUROLYZER® S1 Pro Set (O2E, CO/H2+, Draft, Pressure)

Professional and robust flue gas analyzer set for servicing and inspecting oil, gas and pellets-fired heating systems.  


to the product